mySCADA
myDESIGNER › myDESIGNER › Connections & Protocols

Modbus - 32-bit integers

The long integers are implemented in the same manner as the floating-point numbers.

RegisterMappingSwap modeBytes in 2 16 - bit registersResulting 32 - bit floating point
HdHolding registersN/A[a b][c d][a b c d]
HdsHolding registersByte and word swap[a b][c d][d c b a]
HdsbHolding registersByte swap[a b][c d][b a d c]
HdswHolding registersWord swap[a b][c d][c d a b]
RdInput registersN/A[a b][c d][a b c d]
RdsInput registersByte and word swap[a b][c d][d c b a]
RdsbInput registersByte swap[a b][c d][b a d c]
RdswInput registersWord swap[a b][c d][c d a b]